Smoke exhaust systems are essential in HVAC fire protection, ensuring that during a fire, smoke and toxic gases are safely extracted to protect occupants and maintain clear evacuation routes. A well-designed smoke control system saves lives, protects property, and meets international fire safety codes. For HVAC engineers, contractors, and system integrators, understanding these standards is critical to ensure compliance and reliability.
Smoke exhaust systems remove heat, smoke, and toxic gases during fire incidents to maintain visibility and protect escape routes. Proper design follows EN 12101, NFPA 92, and UL 864 standards, ensuring ducts, fans, and dampers withstand high temperatures. Key design factors include airflow rate, pressure balance, damper control, and fire-rated duct materials. Certified systems ensure compliance with international fire safety regulations and enhance life safety in commercial and industrial buildings.
Let’s explore how to design efficient, code-compliant smoke exhaust systems that integrate seamlessly with HVAC networks while meeting EN, NFPA, and UL safety standards.
A smoke exhaust or smoke control system is a network of ducts, fans, dampers, and sensors designed to extract smoke and heat from buildings during a fire. The goal is to maintain tenable conditions for safe evacuation and fire-fighting operations. It’s especially critical in high-rise, underground, and commercial buildings where smoke movement can quickly block exits.
A complete smoke exhaust system includes:
Smoke exhaust fans: High-temperature fans that operate up to 300°C for 2 hours (EN 12101-3 certified).
Smoke dampers: Control air and smoke flow between zones, often integrated with fire dampers.
Smoke exhaust ducts: Fire-rated ducts that transport smoke to the outside safely.
Control panels (UL 864): Manage damper and fan activation during fire events.
Pressure relief dampers: Maintain pressure differences in stairwells and escape routes.
Smoke exhaust systems are regulated by multiple international standards:
EN 12101 Series (Europe): Defines design, testing, and performance of smoke control systems.
NFPA 92 (U.S.): Provides guidelines for smoke control systems in buildings.
UL 864: Specifies control panel and actuator safety for smoke and fire systems.
ISO 21927: Covers performance requirements for smoke and heat control components.
Pressurization systems create positive pressure in stairwells or escape routes to keep smoke out. Smoke exhaust systems extract smoke from fire zones or atriums. Both systems often work together for effective smoke management.
Typical design pressures: - Pressurization: 50–60 Pa for stairwells. - Exhaust: 10–15 air changes per hour in fire zones.
Smoke exhaust airflow depends on fire size, heat release rate, and building volume. Designers use the following parameters:
Fire size (Q): Heat output in kW or MW.
Airflow (m³/s): Determined to maintain smoke layer below 2.5 m from floor in evacuation areas.
Temperature: Systems must sustain performance at 250–600°C, depending on building type.
Calculation references: NFPA 92, Annex B and EN 12101-5.
Duct materials must be fire-resistant, airtight, and capable of maintaining structural integrity at high temperatures.
Galvanized steel: Standard choice for general applications.
Stainless steel: Preferred in corrosive or high-humidity environments.
Fire-rated composite ducts: Lightweight options with insulation layers (EI60–EI120 rated).
Insulated joints and flexible connectors: Prevent vibration and leakage
Installation must follow EN 12101-3 and UL 705 guidelines:
Mount fans outside the fire zone whenever possible.
Install vibration isolators and flexible connections.
Ensure smoke dampers are accessible for testing and maintenance.
Provide manual override control at fire command center.
Label all components with identification numbers and test ratings.
Smoke control systems rely on dedicated control panels certified under UL 864 (UUKL listed). These panels manage:
Automatic damper activation via fire alarm signals.
Manual fan control for smoke extraction or pressurization.
Feedback monitoring for open/close position of dampers.
Temperature and pressure sensors for fault detection.
Integration with the Building Automation System (BAS) allows real-time monitoring and remote testing.
Testing verifies that all components operate correctly during fire conditions:
Functional test: Simulate fire alarm signal to trigger fans and dampers.
Airflow test: Measure air volume and pressure in ducts and exhaust points.
Temperature endurance test: Run fans at 300°C for 2 hours per EN 12101-3.
Control test: Verify feedback signals reach the fire control room.
Maintenance intervals per NFPA 92 (Chapter 8) and EN 12101-6:
Visual inspection every 6 months.
Full operational test annually.
Fan and actuator service every 2 years.
Comprehensive re-certification every 5 years.
Smoke exhaust systems must coordinate with fire dampers to control airflow paths. When a fire is detected:
Fire dampers close in unaffected zones.
Smoke exhaust dampers open in the fire zone.
Fans activate to extract smoke and maintain pressure differential.
Integration is achieved via UL 864-listed control panels connected to fire damper control systems and building management software.
Before final project approval, contractors must provide:
EN 12101 or UL 864 compliance certificates for each component.
Performance test reports for fans and dampers.
System design drawings and airflow calculations.
Inspection and maintenance plan per NFPA 92.
Operation & Maintenance (O&M) manual with control logic.
The EN 12101 standard series covers smoke and heat control systems: Part 3 – Fans, Part 6 – Pressure differential systems, Part 7 – Ducts, and Part 8 – Dampers. Each component must bear a CE mark to confirm conformity.
NFPA 92 provides formulas for calculating smoke exhaust rates, pressure balance, and temperature rise. It also defines testing, maintenance, and documentation procedures.
UL 864 covers fire alarm and smoke control system control units. Compliance ensures electrical safety, performance reliability, and interoperability between HVAC and fire systems.
Fire-rated ducts and dampers should form a continuous smoke-tight system. Use only assemblies tested together under EN 1366-1 or UL 555 to ensure certification validity.
Smoke exhaust fans are typically rated for F200, F300, or F400 classes depending on endurance. Designers must specify the appropriate class based on building type and fire risk level.
Smoke exhaust system design is a cornerstone of modern HVAC fire protection. Following EN 12101, NFPA 92, and UL 864 standards ensures performance, reliability, and compliance with international codes. By integrating high-quality fire dampers, ducts, and fans, engineers can deliver safe, efficient, and certifiable systems for any building project.
We supply EN 12101- and UL 864-certified smoke exhaust systems, including high-temperature fans, ducts, and damper control units. Our products are designed for international compliance, fast delivery, and OEM customization to meet specific HVAC fire protection requirements.